GIC PT100 Temperature control relay, SPCO, 2AI, Din, 24VAC/DC
Subcribe to back in stock notification
Temperature Controllers, as the name suggests, are used to control temperature. GIC manufactures ON/OFF Temperature Controllers that follow a very simple principle. To elaborate on the principal, after a set point is fixed for heating control, the output is switched on when the temperature is below the set point and switched off when it is above the set point to keep the temperature at a desired level.
- Wide operating Supply Range 24V to 240V AC/DC.
- Two analog outputs of 0 to 10V DC.
- Sensor Fault detection (open/short) indication through LED’s as well as Analog outputs.
- LED Indications for power ON and relay ON status display.
- Adjustable wide temperature range from -50°C to 300°C through DIP switches.
- Auto/Manual reset mode selectable through DIP switch.
- Relay Normal/Inversion mode selectable through DIP switch.
- High load switching capacity of output up to 10A.
Parameters
Supply voltage: 24V to 240V AC/ DC ( ±15%)
Supply frequency: 50/60Hz
Power consumption(Max): For AC <5 VA For DC approx. 1W 10 Ohm per Lead
Device characteristics
Max lead resistance compensated in 3 wire Pt-100 Sensor: 10 Ohm per Lead
Max error in 2 wire sensor: 2.6°C per Ohm
Temperature trip accuracy: ±1°C
Temperature drift: Max 0.05°C/°C
Temperature ranges: -50°C to 50°C, 0°C to 100°C, 100°C to 200°C, 200°C to 300°C
Set point: 0%-20%-40%-60%-80%-100%
Hysteresis: 2%-5%-8%-11%-14%-17%-20%
Sensor fault: Open and Short (Relay OFF)
Sensor fault detection time: <500 ms
Sensor fault recovery time: 1.8 to 2 sec.
Output characteristics
Contact arrangement: 1 C/O
Contact ratings: 10A @ 250VAC / 30VDC, 4KV Isolation between Coil & Contact.
Utilization category: AC-15: 3A /250V AC
Response time(Trip Delay): min 600 ms to 1 sec
Analogue output details
Measured point (Y1): (0-10) VDC ± 200 mV
Set Point (Y2): (0-10) VDC ± 100 mV
Ambient conditions
Operating temperature: -10°C to +55°C
Storage temperature: -15°C to +60°C
Degree of protection: IP 20 for terminals & IP 40 for Enclosure
Relative humidity: 5 to 85% RH(non-condensation)
Max. altitude: 2000 m
Pollution degree: II
Type of insulation: Reinforced