Schneider RCCB, type AC, 2-pole, 30mA, 80A
Acti9-Residual current circuit breaker-iID
The Acti9-Residual current circuit breaker-iID is designed to protect people against electric shocks by detecting and interrupting fault currents. The functional unit of this product is designed to turn off all or part of an installation by separating the installation or part of the installation from all electrical energy or earth for safety reasons.
The iID range is rated for a voltage range of 220-240V AC with a frequency of 50/60 Hz and a rated current of 80A. This circuit breaker provides isolation, characterized by a rated voltage of 500V AC with a frequency of 50/60 Hz, and it is designed to provide this function for 20 years.
Overall, the Acti9-Residual current circuit breaker-iID is a reliable and effective solution for protecting people against electric shocks. It is designed to detect and interrupt fault currents, and its rated voltage and current make it suitable for use in a variety of electrical installations. Additionally, its 20-year lifespan ensures its longevity and reliability.
Parameter
Range: Acti 9
Product name: Acti 9 iID
Product or component type: Residual current circuit breaker (RCCB)
Device short name: IID
Electrical data
[In] rated current: 80 A
Earth-leakage sensitivity: 30 mA
Network frequency: 50/60 Hz
[Ue] rated operational voltage: 220...240 V AC 50/60 Hz
Rated breaking and making capacity: Idm 1500 A, Im 1500 A
Rated conditional short-circuit current: 10 kA
[Ui] rated insulation voltage: 500 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage: 6 kV
Mechanical data
Poles description: 2 P
Neutral position: Left
Network type: AC
Earth-leakage protection time delay: Instantaneous
Earth-leakage protection class: Type AC
Device location in system: Outgoer
Residual current tripping technology: Voltage independent
Control type: Toggle
Mounting mode: Clip-on
Mounting support:
Mechanical durability: 20000 cycles
Electrical durability: AC-1: 10000 cycles
Locking options description: Padlocking device
Wire stripping length: 14 mm for top or bottom connection
Tightening torque: 3.5 N.m top or bottom
Ambient conditions
Operating temperature range: -5…60 °C
IP degree of protectionIP20 conforming to IEC 60529