GIC Earth leakage relay, 2c/o, 220 - 415VAC, 30mA - 30A
Subcribe to back in stock notification
- Monitors, Detects and Protects Power systems from Earth Leakage Faults
- Wide range of selectable Earth Leakage Current: 30 mA - 30 A
- Configurable Earth Leakage Trip time: 0 - 10 s
- Wide Auxiliary Supply Range: 110 - 240 V AC / DC, 220 - 415 V AC / 220 V DC
- Instantaneous Trip for 5 times of set value of Leakage current
- Test feature to check complete product functionality
- LED Indication for Relay status, CT open, Earth Leakage fault & Test/Reset switch feature
- Manual / Remote Reset feature
- 1 C/O + 1 NO Relay Output
Parameters
Supply voltage:220 - 415V AC / 220V DC
Supply variation: -20 to +10%
Frequency: 50/60 Hz
Power consumption (Max.): 10 VA
Leakage current range: 30 mA to 30 A
Threshold:
For '17G7' devices: 0.03 - 0.1 - 0.3 - 0.5 - 1 - 3 - 5 - 10 - 20 - 30
For '17G8' devices: 0.03 - 0.05 - 0.1 - 0.3 - 0.5 - 0.75 - 1- 3 - 5 - 10
Type class: 'A' True RMS measurement (As per IEC 60947-2 appendix M) up to I N= 3A
Max. crest factor: 5 (for 30 mA to 30 A)
Reset mode: Auto Reset
No. of resets: 4
Clear auto reset: After 1 hour of healthy condition or supply interruption
Reset enable & reset time: Below 50% of set current threshold in presence of CBCT
Trip time: 0 - 0.06 - 0.15 - 0.25 - 0.5 - 0.8 - 1 - 2.5 - 5 - 10
Test / reset: Local & Remote (Non Potential free contacts, upto 10 m)
Setting accuracy: -20% (Including CBCT Accuracy)
Repeat accuracy: ± 2%
Output
Relay output: 1 C/O + 1 NO
Contact rating: 5A @ 240V AC / 30V DC (Resistive)
Electrical life: 1X10
Mechanical life: 1X10
Utilization category
AC - 15 Rated voltage (Ue): 120/240 V, Rated current (Ie): 3.0/1.5 A
DC - 13 Rated voltage (Ue): 24/125/250 V, Rated current (Ie): 2.0/0.22/0.1 A
Operating temperature
Storage temperature: -25°C to + 80°C
Humidity (Non Condensing): 95% (Rh)
Enclosure: Flame Retardant UL94-V0
Dimension (W x H x D): 36 X 90 X 65mm
Weight (unpacked) approx.: 150 g
Mounting: Base / DIN rail
Degree of protection: IP 20 for Terminals, IP 40 for Enclosure
Certification / Standard
EMI / EMC
- Harmonic Current Emissions IEC 61000-3-2
- ESD IEC 61000-4-2
- Radiated Susceptibility IEC 61000-4-3
- Electrical Fast Transients IEC 61000-4-4
- Surges IEC 61000-4-5
- Conducted Susceptibility IEC 61000-4-6
- Voltage Dips & Interruptions (AC) IEC 61000-4-11
- Conducted Emission CISPR 11
- Radiated Emission CISPR 11
Environmental
- Cold Heat IEC 60068-2-1
- Dry Heat IEC 60068-2-2
- Vibration IEC 60068-2-6
- Repetitive Shock IEC 60068-2-27
- Non-Repetitive Shock IEC 60068-2-27