SITOP PSU200M is ideal for complex plants and machines. The wide-range input allows it to be connected to any supply system and also to withstand large voltage fluctuations. The power boost briefly delivers up to three times the rated current. And in the event of an overload, you can choose between constant current with automatic restart or latching shutdown. The high degree of efficiency reduces energy consumption, while the compact metal enclosure saves space.

Specifications

Design: SITOP PSU200M

Nominal value output current: 10.0 A

Rated voltage range: 230 to 120V AC

Rated frequency: 50 to 60 Hz


Input current

Input: 1-phase and 2-phase AC

Input voltage: 1) 85 ... 264 V AC , 2)176 ... 550 V AC

Supply voltage: 1) 8120 ... 230 V AC , 2)230 ... 500 V AC

Overvoltage resistance: 1300 Vpeak, 1.3 ms

Input current at rated input voltage 500 V: 1 A

Mains buffering: at Vin = 120/230 V, typ. 150 ms at Vin = 400 V

Mains buffering at Iout rated, min: 25 ms; at Vin = 120/230 V, typ. 150 ms at Vin = 400 V


Output current

Output: Controlled, isolated DC voltage

Output voltage: 480 V

Rated voltage Vout DC: 24 V DC

Total tolerance, static: ±3 %

Static mains compensation, approx.: 0.1 %

Static load balancing, approx: 0.1 %

Residual ripple peak-peak, max.: 50 mV

Spikes peak-peak, max. (bandwidth: 20 MHz): 200 mV

Adjustment range: 24 ... 28.8 V

Status display:Green LED for 24 V OK

SignalingRelay contact: (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK"

Startup delay, max.: 1 s

Voltage rise, type.: 50 ms

Rated current value Iout rated: 10 A

Current range: 0 ... 10 A -+60 ... +70 °C: Derating 2%/K (at 120 V, 230 V) or 3.5%/K (at 400 V)

Supplied active power typical: 240 W

Short-term overload current: 30 A

Duration of overloading capability for excess current: 25 ms

Constant overload current (start-up typical): 12 A


Efficiency

Efficiency at Vout rated, Iout rated, approx.: 91 %

Power loss at Vout rated, Iout rated, approx.: 24 W


Mechanical data

Output overvoltage protection: <35 V

Current limitation, type: 12 A

Dimensions of enclosure (W x H x D): 70 x 125 x 125mm

Humidity class: Climate class 3K3, 5 … 95% no condensation

Connection: screw-type terminals


Ambient conditions

Operating temperature: -25 °C - 70 °C

Protection rating: IP20

Other parts