GIC Voltage Monitoring Series Sm 175

GIC

  • Description
  • Specifications
  • Other parts
  • Documents

Description

GIC offers a variety of voltage monitoring relays that are built for the sole purpose of protecting your equipment against the damaging effects of abnormal voltage conditions and fluctuations.

  • Compact 17.5 mm (Width)
  • Multi-Voltage: Three Phase 3 Wire @ 208-480V AC or Three Phase 4 Wire @ 120-277V AC
  • Can be configured for 3 Phase 3 Wire or 3 Phase 4 Wire system
  • Protection against Phase loss, Phase Sequence, Phase Asymmetry, Under Voltage & Over Voltage
  • Selectable Under Voltage / Over Voltage, Asymmetry, and Phase Sequence
  • LED Indication for all Faults & change in dip switch settings during runtime for better security 
  • Adjustable ON/OFF Time Delay in seconds/minutes
  • 1 C/O Configuration

Specifications

Parameters

Supply voltage: 208 to 480 VAC (3P, 3W)

Supply variation: -12% to + 10%/- 23%

Frequency: 50/60 Hz

Power consumption (Max.): 3.5A

Settable nominal voltage: 208 - 220 - 380 - 400 - 415 - 440 - 480 V AC


Trip settings

Phase loss: Yes

Phase sequence: Yes

Under Voltage: -2% to -20%

Over voltage: -2% to 20%


Time delay

ON delay: 5 sec

Trip time (OFF Delay): 0.5 to 15s (selectable)


Output

Relay output: 1 C/O

Contact rating: 5A @ 250V AC / 30V DC (Resistive)

Electrical life: 5X10

Mechanical life: 1X10


Utilization category

AC - 15    Rated Voltage (Ue): 120/240 V, Rated Current (Ie): 3.0/1.5 A

DC - 13    Rated Voltage (Ue): 24/125/250 V, Rated Current (Ie): 2.0/0.22/0.1 A


Temperature

Operating temperature: -15°C to + 60°C

Storage temperature: -20°C to + 70°C

Humidity (Non Condensing): 95% (Rh)

Enclosure:  Flame Retardant UL94-V0

Dimension (W x H x D): 18 X 59X 90mm

Weight (unpacked) approx.: 70 g

Mounting: Base / DIN rail

Degree of Protection: IP 20 for Terminals, IP 30 for Enclosure



Certification / Standard

EMI / EMC

  • Harmonic Current Emissions IEC 61000-3-2
  • ESD IEC 61000-4-2
  • Radiated Susceptibility IEC 61000-4-3
  • Electrical Fast Transients IEC 61000-4-4
  • Surges IEC 61000-4-5
  • Conducted Susceptibility IEC 61000-4-6
  • Voltage Dips & Interruptions (AC) IEC 61000-4-11
  • Conducted Emission CISPR 11
  • Radiated Emission CISPR 11



Environmental

  • Cold Heat IEC 60068-2-1
  • Dry Heat IEC 60068-2-2
  • Vibration IEC 60068-2-6
  • Repetitive Shock IEC 60068-2-27
  • Non-Repetitive Shock IEC 60068-2-27

Other parts