GIC Voltage Monitoring Series Sm 175

GIC

  • Description
  • Specifications
  • Other parts
  • Documents

Description

GIC offers a variety of voltage monitoring relays that are built for the sole purpose of protecting your equipment against the damaging effects of abnormal voltage conditions and fluctuations.

  • Compact 17.5 mm (Width)
  • Multi-Voltage: Three Phase 3 Wire @ 208-480V AC or Three Phase 4 Wire @ 120-277V AC
  • Can be configured for 3 Phase 3 Wire or 3 Phase 4 Wire system
  • Protection against Phase loss, Phase Sequence, Phase Asymmetry, Under Voltage & Over Voltage
  • Selectable Under Voltage / Over Voltage, Asymmetry, and Phase Sequence
  • LED Indication for all Faults & change in dip switch settings during runtime for better security 
  • Adjustable ON/OFF Time Delay in seconds/minutes
  • 1 C/O Configuration

    Specifications

    Parameters

    Supply voltage: 208 to 480 VAC (3P, 3W) - 120 to 277 VAC (3P, 4W)

    Supply variation: +/- 23%

    Frequency: 50/60 Hz

    Reference voltage: Settable


    Trip settings

    Phase loss: Yes

    Phase sequence: > Yes

    Phase asymmetry: 10% Fixed

    Under voltage: 2% to 22%

    Over voltage: 2% to 22%

    Hysterisis (Phase Asy.): 2.7% Fixed

    Hysterisis (UV/OV): 2% Fixed

    Power consumption (Max.): 16 VA @ 415V AC


    Time delay

    ON delay: (0 to 15 Sec) settable / 5 sec (selectable DIP switch)

    Trip time (OFF Delay): 5 sec / (0 to 15 Sec) settable (selectable DIP switch), 100ms max for Phase loss & Phase Sequence


    Output

    Relay output: 1 C/O

    Contact rating: 5A @ 250V AC / 30V DC (Resistive)

    Electrical life: 5X10

    Mechanical life: 1X10


    Utilization category

    AC - 15     Rated Voltage (Ue): 120/240 V, Rated Current (Ie): 3.0/1.5 A

    DC - 13     Rated Voltage (Ue): 24/125/250 V, Rated Current (Ie): 2.0/0.22/0.1 A


    Temperature

    Operating temperature: -20°C to + 60°C

    Storage temperature: -25°C to + 70°C

    Humidity (Non Condensing): 95% (Rh)

    Enclosure:  Flame Retardant UL94-V0

    Dimension (W x H x D):  18 X 90 X 66.5mm

    Weight (unpacked) approx.: 72 g

    Mounting: Base / DIN rail

    Degree of protection: IP 20 for Terminals, IP 40 for Enclosure



    Certification / Standard


    EMI / EMC

    • Harmonic Current Emissions IEC 61000-3-2
    • ESD IEC 61000-4-2
    • Radiated Susceptibility IEC 61000-4-3
    • Electrical Fast Transients IEC 61000-4-4
    • Surges IEC 61000-4-5
    • Conducted Susceptibility IEC 61000-4-6
    • Voltage Dips & Interruptions (AC) IEC 61000-4-11
    • Conducted Emission CISPR 11
    • Radiated Emission CISPR 11



    Environmental

    • Cold Heat IEC 60068-2-1
    • Dry Heat IEC 60068-2-2
    • Vibration IEC 60068-2-6
    • Repetitive Shock IEC 60068-2-27
    • Non-Repetitive Shock IEC 60068-2-27


    Other parts