GIC Electronic Timer - Series Micon 225

GIC

  • Description
  • Specifications
  • Other parts
  • Documents

Description

  • Multi-function with Signal Start and Supply Start.
  • 16 Timing Functions selected by DIP switch.
  • Two independent relay outputs with either both relays timed or one timed and one instantaneous.
  • Wide Input Signal & Supply range - 24–240V AC/DC.
  • Wide Timing Range - 0.1s to 120 days.
  • High timing accuracy.
  • LED indicators for Power Supply & Relay Status.
  • 22.5mm DIN Mount Housing.

Specifications

Parameters

Supply voltage: 24 - 240V AC / DC

Supply variation: -20% to +10%

Frequency: 50/60 Hz

Power consumption (Max.): < 2 VA @ 24 VAC / DC, < 4 VA @ 230V AC / DC

Initiate time: 100 ms (Max.)

Reset time: 200 ms (Max.) 

Input signals / signal isolation:

High Range: 85-265V AC, 100-265V DC(B1H-A2), Low Range: 24-60V AC/DC (B1L-A2)

Signal sensing time: For AC Signals: 50 ms Max. and For DC Signals: 20 ms Max.

Signal stabilization delay: 100 ms (Applicable at Power ON Only)

Setting accuracy: ± 5% of Full scale

Repeat accuracy: ± 1%

 

Output

Relay output: 1 C/O (Delayed) & 1 C/O (Configurable as either Delayed or Instant)

Contact rating: 5A for NO & 3A for NC @ 250V AC / 30VDC (Resistive)

Contact material: AgNi

Electrical life:  1x10

Mechanical life: 1x10 

Set time (Ts): 0.1 seconds to 120 Days

LED indication on front panel: Green LED ON: Power ON, Amber LED ON :Relay ON for Delayed contact

Mounting: Base / DIN Rail

Max. operating altitude: 2000m

Housing: Flame retardant (UL 94-V0)


Temperature

Operating temperature: -10° C to +60° C

Storage temperature: -20° C to +70° C

Humidity (Non Condensing): 95% (Rh)

LED indication: Green LED  -  Power ON, Red LED - Relay ON

Enclosure: Flame Retardant UL94-V0

Dimension (W x H x D): 22.5 X 75 X 100.5 mm

Weight (unpacked) Approx.: 153 g

Pollution degree: II

Degree of Protection: IP 20 for Terminals, IP 40 for Enclosure


Certification / Standard

  • Harmonic current emissions IEC 61000-3-2
  • ESD IEC 61000-4-2
  • Radiated susceptibility IEC 61000-4-3
  • Electrical fast transients IEC 61000-4-4
  • Surges IEC 61000-4-5
  • Conducted susceptibility IEC 61000-4-6
  • Voltage dips & interruptions (AC) IEC 61000-4-11
  • Conducted emission CISPR 14-1
  • Radiated emission CISPR 14-1

Safety

  • Test voltage between I/P and O/P IEC 60947-5-1
  • Test voltage between all terminals & enclosure IEC 60947-5-1
  • Impulse voltage between I/P and O/P IEC 60947-5-1
  • Single fault IEC 61010-1
  • Insulation resistance UL 508
  • Leakage current UL 508
  • Product reference Standard IEC 61812-1


Environmental

  • Cold heat IEC 60068-2-1
  • Dry heat IEC 60068-2-2
  • Vibration IEC 60068-2-6
  • Repetitive shock IEC 60068-2-27
  • Non-Repetitive Shock IEC 60068-2-27